1673-159X

CN 51-1686/N

谭礼斌, 袁越锦, 黄灿, 余千英, 刘小强. 基于STAR-CCM+的发电机组流场对比分析及结构优化[J]. 西华大学学报(自然科学版), 2019, 38(4): 77-82, 99. DOI: 10.3969/j.issn.1673-159X.2019.04.012
引用本文: 谭礼斌, 袁越锦, 黄灿, 余千英, 刘小强. 基于STAR-CCM+的发电机组流场对比分析及结构优化[J]. 西华大学学报(自然科学版), 2019, 38(4): 77-82, 99. DOI: 10.3969/j.issn.1673-159X.2019.04.012
TAN Libin, YUAN Yuejin, HUANG Can, YU Qianying, LIU Xiaoqiang. Flow Field Comparison Analysis and Structure Optimization Research of a Generator Unit Using STAR-CCM+[J]. Journal of Xihua University(Natural Science Edition), 2019, 38(4): 77-82, 99. DOI: 10.3969/j.issn.1673-159X.2019.04.012
Citation: TAN Libin, YUAN Yuejin, HUANG Can, YU Qianying, LIU Xiaoqiang. Flow Field Comparison Analysis and Structure Optimization Research of a Generator Unit Using STAR-CCM+[J]. Journal of Xihua University(Natural Science Edition), 2019, 38(4): 77-82, 99. DOI: 10.3969/j.issn.1673-159X.2019.04.012

基于STAR-CCM+的发电机组流场对比分析及结构优化

Flow Field Comparison Analysis and Structure Optimization Research of a Generator Unit Using STAR-CCM+

  • 摘要: 文章以康明斯6C柴油发电机组(机组型号S688CCS)为研究对象,采用STAR-CCM+分析软件对该发电机组常规型和静音型的整机流场进行分析,对比研究该发电机组2种类型流场的差异性。模拟结果表明:该机组静音型的冷却风总量低于其常规型机组,且散热器处冷却风也低于常规型机组,不利于机组散热。依据流场对比分析的结果,采用单一变量控制方法,对静音型机组的风扇罩、消音材料及附近结构、进气格栅等结构进行改进,优化了流场分布特性,从而提出了相应的结构优化方案。优化后静音型机组散热器的风量较初始结构下的散热器风量提升44.33%,冷却风总量高于常规型机组,提升比例较大。研究结果可为发电机组冷却风道的设计提供相应的理论依据。

     

    Abstract: A Cummins 6C diesel generator unit (S688CCS) is taken as the research object in this paper and the fluid dynamics analysis software STAR-CCM+ is applied for conducting the numerical simulation study on flow field distributions of its conventional type and silent type. The difference of fluid distribution characteristics between conventional type generator unit and silent type generator unit is compared. Simulation results indicate the total cooling air of the silent generator is lower than that of the conventional generator, and the cooling air at the radiator is also lower than that of the conventional generator, which is not good for generator cooling. Based on the results of flow field comparison analysis, single variable control method was adopted to improve the structure of fan cover, silent components for silence, adjacent structure and air inlet grille. The flow field distribution characteristics were optimized, and the corresponding structure optimization scheme is put forward. After optimization, the cooing air amount flow through radiator of the silent generator unit is 44.33% higher than that of the radiator of its original structure, and the total amount of cooling air is higher than that of the conventional unit. The research results in this paper can provide a theoretical basis for the design of cooling air flow-path of generator units.

     

/

返回文章
返回